    NYKW2 series intelligent air circuit breaker

    It is mainly used to control and protect LV distribution network. which is normally installed in low-voltage power distribution cabinet for overall protection. Circuit breaker of no more than 1000A rated current could satisfy frequent start of electric motors.

    • AC rated current 630A~6,300A;
    • Short circuit breaking capacity 80kA~120kA(effective values);
    • Rated operating voltage AC690V and below;
    • 3-pole circuit breaker and 4-pole circuit breaker;
    • Drawer type circuit breaker and fixed type circuit breaker;
    • Reversible incoming installation;
    • Various intelligent controllers to realize different functions;
    • Isolation function, sign is"";
    • Carrying out IEC60947-2 and GB14048.2-2008 standards;
    • This circuit breaker has gained China Compulsion Certification "CCC".

    NYKW3 series intelligent air circuit breaker

    • NYKW3-1250 series intelligent air circuit breaker (hereinafter referred to as circuit breaker) has features of compact structure, small volume, high reliability and zero arcing, etc.. Rated insulation voltage of circuit breaker is 690V, applying to AC 50Hz, 400V rated working voltage and 200A-1250A rated current. It’s mainly used in distribution network to distribute electricity, protect circuit and power supply equipment from over-load, under-voltage, short circuit and single-phase grounding fault hazards.
    • The circuit breaker is a three-dimensional arrangement, contact system of every phase is closed inside insulation base, forming a small independent chamber. These chambers constitute main circuit of circuit breaker.
    • Technical performance of circuit breaker conforms to standards of GB14048.2 Low-Voltage Switch Equipment and Controlling Equipment Low-Voltage Circuit Breaker and IEC60947-2 Low-Voltage Switch Equipment and Controlling Equipment Secondary Low-Voltage Circuit Breaker.

    Main Specifications and Technical Parameters

    Main Specifications and Technical Parameters of NYKW2 Series

    Type NYKW2-2000
    Frame grade rated current Inm (A) 2000
    Rated current In(A) 630 800 1000 1250 1600 2000
    Rated working voltage Ue(V) AC400,690 50Hz
    Rated insulation voltage Ui(V) AC1000
    Rated impulse withstand voltage Uimp(V) 12000
    Power frequency withstand voltage (V) AC3500V 1min
    Number of poles 3、4 3、4 3、4 3、4 3、4 3、4
    Rated limit short-circuit breaking capacity Icu (kA) (Valid value) AC400V 85 85 85 85 85 85
    AC690V 50 50 50 50 50 50
    Rated operation short-circuit breaking capacity Ics (kA) (Valid value) AC400V 50 50 50 50 50 50
    AC690V 40 40 40 40 40 40
    Rated short-circuit making capacity Icm (kA) (peak) AC400V 176 176 176 176 176 176
    AC690V 105 105 105 105 105 105
    Rated short-time withstand current (1s) Icw (kA) (Valid value) AC400V 50 50 50 50 50 50
    AC690V 40 40 40 40 40 40
    Use category B
    Full breaking time (no additional delay) (ms) 12-18
    Closing time (ms) Max. 70
    Intelligent controller Electronic type
    Standard type
    Communication type
    Electrical life * (times) AC400V 10000 10000 10000 10000 10000 10000
    AC690V 5000 5000 5000 5000 5000 5000
    Mechanical life * (times ) Maintenance-free 10000 10000 10000 10000 10000 10000
    Maintenance needed 20000 20000 20000 20000 20000 20000
    Installation Overall Dimensions (mm) H W L H W L H W L H W L H W L H W L
    Drawer type 3P 432 375 420 432 375 420 432 375 420 432 375 420 432 375 420 432 375 420
    4P 432 470 420 432 470 420 432 470 420 432 470 420 432 470 420 432 470 420
    Fixed type 3P 402 318 325 402 318 325 402 318 325 402 318 325 402 318 325 402 318 325
    4P 402 413 325 402 413 325 402 413 325 402 413 325 402 413 325 402 413 325
    NYKW2-3200 NYKW2-4000 NYKW2-6300
    3200 6300
    2000 2500 2900 3200 3600 4000 4000 5000 6300
    AC400,690 50Hz
    AC1000 50Hz
    12000
    AC3500V1min 50Hz
    3、4 3、4 3、4 3、4 3、4 3、4 3、4 3、4 3
    50%In、100%In
    100 100 100 100 100 100 120 120 120
    65 65 65 65 65 65 80 80 80
    65 65 65 65 65 65 100 100 100
    50 50 50 50 50 50 65 65 65
    220 220 220 220 220 220 264 264 264
    143 143 143 143 165 165 165 165 165
    65 65 65 65 65 65 100 100 100
    50 50 50 50 50 50 65 65 65
    B
    12-18
    Max 70
    10000 10000 10000 10000 10000 10000 500 500 500
    5000 5000 5000 5000 5000 5000 500 500 500
    10000 10000 10000 10000 10000 10000 2000 2000 2000
    20000 20000 20000 20000 20000 20000 8000 8000 8000
    H W L H W L H W L H W L H W L H W L H W L H W L H W L
    432 435 420 432 435 420 432 435 420 432 435 420 432 550 493 432 813 493 432 813 493 432 928 493
    432 550 420 432 550 420 432 550 420 432 550 420 432 788 493 432 928 493 432 928 493 — —
    402 422 325 402 422 325 402 422 325 402 422 325 — — — — — — — —
    402 515 325 402 515 325 402 515 325 402 515 325 — — — — — — — —

    Main Specifications and Technical Parameters of NYKW3 Series

    Type NYKW3-1250
    Frame grade rated current Inm (A) 1250
    Rated current In(A) 200 400 630 800 1000 1250
    Rated working voltage Ue(V) AC400 50Hz
    Rated insulation voltage Ui(V) AC690
    Rated impulse withstand voltage Uimp(V) 6000
    Power frequency withstand voltage (V) Main circuit AC2500
    Number of poles 3、4 3、4 3、4 3、4 3、4 3、4
    N phase rated current (A) 50%In、100%In
    Rated limit short-circuit breaking capacity Icu (kA) (Valid value) AC400V 65 65 65 65 65 65
    Rated operation short-circuit breaking capacity Ics (kA) (Valid value) AC400V 50 50 50 50 50 50
    Rated short-time withstand current (1s) Icw (kA) (Valid value) AC400V 50 50 50 50 50 50
    Full breaking time (no additional delay) (ms) 12-18
    Closing time (ms) Max. 70
    Electrical life * (times) AC400V 10000 10000 10000 10000 10000 10000
    Mechanical life * (times ) Maintenance-free 10000 10000 10000 10000 10000 10000
    Maintenance needed 20000 20000 20000 20000 20000 20000
    Installation Overall Dimensions (mm) H W L H W L H W L H W L H W L H W L
    Drawer type 3P 362 276 323 362 276 323 362 276 323 362 276 323 362 276 323 362 276 323
    4P 362 346 323 362 346 323 362 346 323 362 346 323 362 346 323 362 346 323
    Fixed type 3P 315 266 239 315 266 239 315 266 239 315 266 239 315 266 239 315 266 239
    4P 315 336 239 315 336 239 315 336 239 315 336 239 315 336 239 315 336 239